Send Email
Send SMS
Search
NRS Solutions A Co.
NRS Solutions A Co.


Fire Alarm Panel

An automatic fire alarm panel is designed to detect the unwanted presence of fire by monitoring environmental changes associated with combustion. We offer Automatic Fire Alarm Panel and Fire Alarm Control Panel.

2 Zone Panel - Ravel

REQUEST CALLBACK

2 Zone Panel - Ravel
Approx. Rs 4,200 / Piece(s)
Get Best Quote

1. Power Supply:
AC Input Supply : 220 V AC, 50Hz
DC Input Supply : 24 V DC

2. Operating Conditions : -10 to 45 C, 95 % RH Max.

3. Operating Voltage : 24 V DC

4. Normal Loop Voltage : 20.7 DC

5. Open Threshold Current : 4.2 mA

6. Short Circuit Threshold Current : 40 mA

7. Stand by Threshold Current : 8.2 mA
( EOL Current + detector's Current)

8. Alarm Current : 20 - 35 mA

9. Quiescent Current : 60mA

10. Colour of the Panel : Broken White (Red, Red Texure - Optional)

11. Panel Size : 350 X 250 X 100(Width X Height X Depth)

12. Approximate Weight : 4Kgs.

13. ALARM OUTPUT: Common Hooter Output : 24V@1A.

14. REMOTE OUTPUTS:
Output : Fire, Fault Relay Contacts (30V AC/ DC @ 2A contact).
  • Item Code: Re-102
  • Minimum Order Quantity: 1 Piece(s)
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: chennai
  • Production Capacity: 3
  • Delivery Time: 7 days from the date of receipt of firm PO
  • Yes! I am Interested

    4 Zone Fire Alarm Panel

    REQUEST CALLBACK

    4 Zone Fire Alarm Panel
    Approx. Rs 7,400 / Piece(s)
    Get Best Quote

    Features

    • As per IS -15908: 2011 Standard.
    • 16 X 2 Dot Matrix LCD Display.
    • Standby battery backup with built in charging.
    • Fire / Fault status in unambiguous colored LED indication.
    • Switch Mode Power Supply.
    • Tactile Keypad for easy panel operation.
    • System on indication.
    • Main, Standby status indication.
    • Low Battery visual warning with audible tone.
    • Relay output for actuators for Fire and Fault.
    • Lamp Test facility
    • Zone wise one man walk Test Facility.
    • Zone wise Isolation facility with loop voltage cut off.
    • Compatible to all type of Conventional Detectors.
    • Optional Zone Wise Sounder / Zone Wise Contact.
    Electrical Specification
    Primary Power
    120 – 220VAC , 50 Hz
    Common Relays
    Type : Form C
    No of Relays : 3
    Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @125VAC.
    Power Factor : 1
    Standby Power
    24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).
    Quiescent current : 55mA
    Operating Condition
    Operating Temperature : 0 – 49° C/32-120° F.
    Relative Humidity : 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F.
    Initiating Device Circuits (Zone Circuit)
    All zones are Class B wiring
    Normal Operating Voltage : 14- 21 VDC
    Alarm Current : 15 – 30mA
    Short Circuit Current : 42mA Maximum
    Loop resistance : 50 ohms Maximum
    End-Of-Line Resistor : 4.7K, 1/4watt
    Standby Current : 6.8mA (2.4mA for Detectors)
    Charging Circuit
    Charging Voltage 28.2V, ±0.5V
    Charging Current 0.5 A (Max.).
    Notification Appliance Circuits
    Class B wiring
    Operating Nominal Voltage : 24VDC
    Current for NACs : 0.6 Amp
    End-Of-Line Resistor : 4K7, 1/4 watt
  • Item Code: RE-104
  • Minimum Order Quantity: 1 Piece(s)
  • Pay Mode Terms: T/T (Bank Transfer)
  • Port of Dispatch: chennai
  • Production Capacity: 3
  • Delivery Time: 7 days from the date of receipt of firm PO
  • Yes! I am Interested

    View PDF

     
    X


    Call Us: +91-8079451459
    NRS Solutions A Co.
    D. Sujatha (Business Development Head)
    Plot No. 295, Burma Colony, 4th Main Road Perungudi,
    Chennai - 600096, Tamil Nadu, India
    Contact via E-mail
    Contact via SMS



    Home  |   Introduction   |  Product Range  |  Site Map  |   Contact Us   |   Mobile Site

    © NRS Solutions A Co.. All Rights Reserved (Terms of Use)
    Developed and Managed by IndiaMART InterMESH Limited

    NRS Solutions A Co.